TrippLite 3kVA SMARTINT3000VS SmartPro 2.25kW Line-Interactive Tower UPS
The TrippLite SMARTINT3000VS SmartPro 3kVA UPS is a robust line-interactive uninterruptible power supply designed to safeguard critical equipment from power disruptions and fluctuations. With a power capacity of 3000 VA (3 kVA) and a wattage rating of 2250 watts (2.25 kW), this UPS provides reliable protection for a range of devices, ensuring uninterrupted power during outages and stabilizing power quality.
This UPS operates with a standard input voltage of 120V AC and offers a broad input voltage range of 83V to 147V AC, making it adaptable to varying power conditions. It features automatic voltage regulation (AVR), which corrects minor voltage deviations to deliver a steady output voltage of 120V AC, maintaining the performance and longevity of connected equipment.
The SMARTINT3000VS utilizes simulated sine wave output and includes a built-in battery system with sealed lead-acid batteries. The UPS supports hot-swappable batteries, allowing for easy battery replacement without interrupting power to connected devices. Depending on the load, the battery runtime can last up to 10 minutes at full load, and it typically takes 4-6 hours to recharge to 90% capacity.
UPC Code |
037332120311 |
UPS Type |
Line-Interactive |
INPUT
Rated input current (Maximum Load) |
15.4A |
Nominal Input Voltage(s) Supported |
230V AC |
UPS Input Connection Type |
C20 inlet |
UPS Input Connection Description |
User supplies input cabling with C19 output connection |
Input Phase |
Single-Phase |
OUTPUT
Output Volt Amp Capacity (VA) |
3000 |
Output kVA Capacity (kVA) |
3 |
Output Watt Capacity (Watts) |
2250 |
Output kW Capacity (kW) |
2.25 |
Output Capacity Details |
Output is reduced to 1500W maximum with 2 or more external battery packs |
Power Factor |
0.75 |
Nominal Voltage Details |
230v nominal inverter output voltage |
Frequency Compatibility |
50 / 60 Hz |
Frequency Compatibility Details |
Automatic frequency selection |
Output Voltage Regulation (Line Mode) |
-19% +8% |
Output Voltage Regulation (Battery Mode) |
+/- 5% |
Included Output Power Cables |
Includes 3 C13 to C14 output power cables |
Load Management Receptacles |
Three switchable two-outlet C13 load banks |
Output Circuit Breakers |
10A (x2) - each breaker protects 4 C13 outlets each, C19 is unbreakered |
Output AC Waveform (AC Mode) |
Sine wave |
Output AC Waveform (Battery Mode) |
PWM sine wave |
Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
Output Receptacles |
(8) C13; (1) C19 |
Individually Controllable Load Banks |
Yes |
BATTERY
Battery Type |
Valve Regulated Lead Acid (VRLA) |
Full Load Runtime (min.) |
4 min. (2250w) |
Half Load Runtime (min.) |
14 min. (1125w) |
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
Expandable Runtime |
Yes |
External Battery Pack Compatibility |
BP48V27-2US (multi-pack compatible); BP48V60RT-3U (multi-pack compatible) |
DC System Voltage (VDC) |
48 |
Battery Recharge Rate (Included Batteries) |
Less than 4 hours from 10% to 90% (typical, full load discharge) |
Battery Access |
Battery access door |
Internal UPS Replacement Battery Cartridge |
RBC54 |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
VOLTAGE REGULATION
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 151V to 282V |
Overvoltage Correction |
Input voltages between 245 and 282 are reduced by 12% |
Undervoltage Correction |
Input voltages between 177 and 199 are boosted by 14% |
Severe Undervoltage Correction |
Input voltages between 151 and 176 are boosted by 30% |
USER INTERFACE, ALERTS & CONTROLS
Switches |
2 Switches control off/on power status and alarm-cancel/self-test operation |
Alarm Cancel Operation |
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status |
Audible Alarm |
Audible alarm indicates power-failure, overload and low-battery conditions |
LED Indicators |
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status |
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating |
480 |
UPS AC Suppression Response Time |
Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |
PHYSICAL
Cooling Method |
Fan |
Installation Form Factors Supported with Included Accessories |
Tower |
Primary Form Factor |
Tower |
Primary UPS Depth (mm) |
305 |
Primary UPS Height (mm) |
361 |
Primary UPS Width (mm) |
234 |
Shipping Dimensions (hwd / cm) |
50.55 x 38.35 x 40.89 |
Shipping Weight (kg) |
30.75 |
UPS Housing Material |
Polycarbonate |
UPS Power Module Dimensions (hwd, cm) |
36.07 x 23.37 x 30.48 |
UPS Power Module Weight (kg) |
27.67 |
ENVIRONMENTAL
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode Efficiency Rating (100% Load) |
94% |
Audible Noise |
Audible Noise < 47dBA At Front Side 1 Meter |
COMMUNICATIONS
Network Management Cards |
SNMPWEBCARD ; TLNETCARD ; WEBCARDLX |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
For local monitoring via the UPSs built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert |
Communications Cable |
2 USB and 2 DB9 cables included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
Communications Interface |
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB |
LINE / BATTERY TRANSFER
Transfer Time |
2-4 milliseconds |
Low Voltage Transfer to Battery Power (Setpoint) |
151 |
High Voltage Transfer to Battery Power (Setpoint) |
282 |
SPECIAL FEATURES
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
High Availability UPS Features |
Hot swappable batteries; Auto Probe Monitoring and Reboot (requires WEBCARDLX) |
STANDARDS & COMPLIANCE
UPS Certifications |
CE |
Certification Details |
CE 62040 |