Eaton 3000VA 9E3000I 9E 2400W 3KVA Tower UPS

by Eaton

KES 191,000 Excl. Tax

Eaton 3000VA 9E3000I 9E 2400W 3KVA Tower UPS

  • Online double conversion topology
  • Intuitive user interface with an LCD panel that provides, on a single screen, clear information about UPS status
  • Reliable UPS at an attractive price
  • Provides more real power (watts) to protect more equipment with a 0.8 power factor
  • Internal bypass and maintenance bypass are available as standards for service continuity
  • Combo input (3:1 and 1:1) on the 10kVA, 15kVA, 20 kVA
  • Long runtime with up to 4 optional EBM cabinets
  • Extra-long runtime available with 3kVA, 10kVA and 20kVA XL models
  • XL models with internal supercharger for extra-long runtime
UPC61UPS0006
Model Number9E3000I
SKU16310

Reviews

This product does not have any reviews yet.

Add your review

Description

Eaton 3000VA 9E3000I 9E 2400W 3KVA Tower UPS 

Eaton 3000VA 9E3000I 9E 2400W 3KVA Tower UPS from the leading UPS dealer in Nairobi kenya, buy online Eaton 3000VA 9E3000I 9E 2400W 3KVA Tower UPS and have it delivered.

Topology Online double conversion
Configuration Tower
Part Number 9E3000I
Rating (VA/Watts) 3000/2400
Dimensions (H x W x D, mm) 399 x 330 x 190
Weight (kg) 24.2
Warranty Warranty 3 Years / 2 Years Battery
 
Electrical Input
Connection
(1) IEC-320-C20
IEC C20
Input Voltage Range 176-300V without derating (up to 100-300V with derating)
Nominal Voltage 208/220/230/240V
Frequency 50/60 Hz autoselection
Frequency Range 40-70 Hz
 
Electrical Output
Voltages 208V*/220V/230V/240V ±1%
Voltage THD <2% for 100% linear load
Outlets
(6) IEC-320-C13
IEC C13
(1) IEC-320-C19
IEC C19
Overload Capacity 105%-130% : 60s, 130%-150% : 10s,>150% : ? 300ms
Efficiency (Normal Mode) Up to 91% in Online mode
Output Frequency 50/60 Hz autoselect
 
Communications
Communication Ports 1 USB port + 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously)
Communication Slot 1 slot for Network-M2, ModBus-MS or Relay-MS cards
Power Management Software Intelligent Power Editions
 
Environmental & Standards
Audible Noise <37 dB @ typical load
Operating Temperature 0 to 40°C
Safety markings IEC/EN 62040-1
EMC Markings IEC/EN 62040 -2
Approvals CE, CB report (TUV)